Energy Performance Certificate

8c, Willoughby Road, IP2 8AP

EPC Report

Energy rating

Current: 60 D | Potential: 76 C
Current Potential A 92–100 B 81–91 C 69–80 D 55–68 E 39–54 F 21–38 G 1–20 60 D Current: 60 D 76 C Potential: 76 C

Environmental impact (CO₂)

Current: 54 | Potential: 76
Current Potential A 92–100 B 81–91 C 69–80 D 55–68 E 39–54 F 21–38 G 1–20 54 Current: 54 76 Potential: 76
Field Value
LMK KEY 8463-7222-5740-9067-3922
ADDRESS1 8c, Willoughby Road
ADDRESS2
ADDRESS3
POSTCODE IP2 8AP
BUILDING REFERENCE NUMBER
CURRENT ENERGY RATING D
POTENTIAL ENERGY RATING C
CURRENT ENERGY EFFICIENCY 60
POTENTIAL ENERGY EFFICIENCY 76
PROPERTY TYPE Flat
BUILT FORM Semi-Detached
INSPECTION DATE 2017-02-23
LOCAL AUTHORITY E07000202
CONSTITUENCY E14001302
COUNTY
LODGEMENT DATE 2017-02-24
TRANSACTION TYPE Rental
ENVIRONMENT IMPACT CURRENT 54
ENVIRONMENT IMPACT POTENTIAL 76
ENERGY CONSUMPTION CURRENT 307
ENERGY CONSUMPTION POTENTIAL 158
CO2 EMISSIONS CURRENT 3.8
CO2 EMISS CURR PER FLOOR AREA 54
CO2 EMISSIONS POTENTIAL 1.9
LIGHTING COST CURRENT 50
LIGHTING COST POTENTIAL 50
HEATING COST CURRENT 703
HEATING COST POTENTIAL 347
HOT WATER COST CURRENT 97
HOT WATER COST POTENTIAL 97
TOTAL FLOOR AREA 69
ENERGY TARIFF Unknown
MAINS GAS FLAG Y
FLOOR LEVEL 3
FLAT TOP STOREY Y
FLAT STOREY COUNT 1
MAIN HEATING CONTROLS Programmer, TRVs and bypass
MULTI GLAZE PROPORTION 100
GLAZED TYPE double glazing installed during or after 2002
GLAZED AREA Normal
EXTENSION COUNT 1
NUMBER HABITABLE ROOMS 3
NUMBER HEATED ROOMS 3
LOW ENERGY LIGHTING 100
NUMBER OPEN FIREPLACES 0
HOTWATER DESCRIPTION From main system
HOT WATER ENERGY EFF Good
HOT WATER ENV EFF Good
FLOOR DESCRIPTION (another dwelling below)
FLOOR ENERGY EFF N/A
FLOOR ENV EFF N/A
WINDOWS DESCRIPTION Fully double glazed
WINDOWS ENERGY EFF Good
WINDOWS ENV EFF Good
WALLS DESCRIPTION Solid brick, as built, no insulation (assumed)
WALLS ENERGY EFF Very Poor
WALLS ENV EFF Very Poor
SECONDHEAT DESCRIPTION None
SHEATING ENERGY EFF N/A
SHEATING ENV EFF N/A
ROOF DESCRIPTION Pitched, 50 mm loft insulation
ROOF ENERGY EFF Poor
ROOF ENV EFF Poor
MAINHEAT DESCRIPTION Boiler and radiators, mains gas
MAINHEAT ENERGY EFF Good
MAINHEAT ENV EFF Good
MAINHEATCONT DESCRIPTION Programmer, TRVs and bypass
MAINHEATC ENERGY EFF Average
MAINHEATC ENV EFF Average
LIGHTING DESCRIPTION Low energy lighting in all fixed outlets
LIGHTING ENERGY EFF Very Good
LIGHTING ENV EFF Very Good
MAIN FUEL mains gas (not community)
WIND TURBINE COUNT 0
HEAT LOSS CORRIDOR no corridor
UNHEATED CORRIDOR LENGTH
FLOOR HEIGHT 2.679
PHOTO SUPPLY 0
SOLAR WATER HEATING FLAG N
MECHANICAL VENTILATION natural
ADDRESS 8c, Willoughby Road
LOCAL AUTHORITY LABEL Ipswich
CONSTITUENCY LABEL Ipswich
POSTTOWN IPSWICH
CONSTRUCTION AGE BAND England and Wales: before 1900
LODGEMENT DATETIME 2017-02-24 15:21:13
TENURE rented (private)
FIXED LIGHTING OUTLETS COUNT 15
LOW ENERGY FIXED LIGHT COUNT 15
UPRN 100091079060
UPRN SOURCE Energy Assessor
REPORT TYPE 2
Source file certificates-2017.csv
COUNTRY England
REGION E12000006
Address display
Nation ew